Fire watch and confined-space attendant duties under Korean workplace safety rules

This is a one-page safety training sheet from KEPCO KPS, a Korean power plant maintenance company. It summarises two requirements of Korea's Rules on Occupational Safety and Health Standards: a fire watch must be posted for welding, cutting and other hot work near flammable materials (Article 241-2), and an attendant must be posted outside any confined space where people work (Article 623). These requirements apply to any employer in Korea, so foreign companies running factories, plants or construction and maintenance sites must staff and equip these roles.

Rules on Occupational Safety and Health Standards (Articles 241-2 and 623)산업안전보건기준에 관한 규칙KEPCO KPS

Key points

  • Work that needs a fire watch Hot work such as welding, cutting and heating metal, and work that may throw sparks, such as dry grinding with a grinding wheel.
  • Locations where a fire watch is required Places with flammable material in the building structure or inside it (including areas open through openings) within an 11 metre work radius. Places with flammable material below the floor that a spark could easily ignite. Places with flammable material against the far side of a metal partition, wall, ceiling or roof that heat conduction or radiation could ignite.

Read the full explanation

  • 6 more points with the exact figures and conditions.
  • Who it affects and what to do about it.
  • Ask IndoyangAI how it applies to your company.

Source

More rules

Source: a document published by a Korean government agency on data.go.kr, under the Korea Open Government License (공공누리). Explained by Indoyang Connect with AI assistance. This is not legal advice: the document may have been updated since, so check the current law before acting.